Nevada Sure Bet Program  2004    

 
 

 

Home
Overview
Recent Updates
Fund Status
Program Benefits
Program Process
Pre_Notification
Eligible Participants
Eligible Projects
Prescriptive Incentives
Custom Incentives
Payment Process
Inspections
Peak Hours
Documents
Incentive Application
Seminars
Contractors
Case Studies
Contact Information

Incentives are available to non-residential customers to help offset the costs of energy efficiency upgrades!

 

           

                                     

 

Prescriptive Incentives

Prescriptive incentives are offered on a per unit basis for common energy saving technologies in the categories of Lighting, Cooling, Motors, Refrigeration and Miscellaneous measures. Some common Prescriptive retrofits include:

q       Compact fluorescent lamps and fixtures

q       Upgrading fluorescent T12 fixtures to T8 or T5 lamps and electronic ballasts

q       Upgrading metal halides (high bay) to T5s

q       De-lamping (permanent fixture retrofit with removal of lamps, ballasts and tombstones)

q       Upgrading incandescent exit signs to low wattage (£5W) LED exit signs

q       LED traffic signals

q       Occupancy sensors to control lighting

q       High EER or SEER package air conditioning units

q       Packaged terminal air conditioning units (PTAC)

q       Room Air Conditioners

q       Set-back thermostats

q       Window film

q       Premium efficiency motors

q       Refrigeration technologies

q       VendingMi$er

q       Photovoltaic modules

 

The following sections detail the eligible measures under the Sure Bet Prescriptive Incentive.

Lighting

Incentives are paid on a per lamp basis, except for the hardwired compact fluorescent fixtures and T5s (paid on a per fixture basis), LED exit signs (paid on a per unit basis) and occupancy sensors (paid on a per sensor basis). Please see the Policies & Procedures for more information.

Prescriptive Lighting Measures

Equipment Type

Incentive/Unit

Replace T12 magnetic ballast with T8/T5 electronic ballast fixtures (per lamp)

2-foot lamp

$2.00

3-foot lamp

$2.75

4-foot lamp

$3.75

8-foot lamp

$7.50

Replace Metal Halide fixture with T5 fixture (per fixture)

T5 fixture

$100

De-lamping (per lamp)

 

2-foot lamp

$1.00

3-foot lamp

$1.00

4-foot lamp

$1.50

8-foot lamp

$2.25

Screw-in Compact Fluorescent Lamps (per lamp)

5-13 watts

$1.50

14-26 watts

$2.00

>= 27 watts

$2.25

Hardwired Fluorescent Fixtures (per fixture)

5-13 watts

$9.00

14-26 watts

$11.00

27-65 watts

$12.00

66-90 watts

$18.00

> 90 watts

$22.00

Exit Signs (per unit)

 

LED or Electroluminescent

$12.50

Traffic Signals (per lamp)

 

LED Signal

$25.00

Occupancy Sensors (per sensor)

 

Wall Box

$8.00

Wall or Ceiling Mount

$20.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Top

Cooling

Air conditioning units that are air, water, or evaporatively cooled split system, single packaged units, PTAC and room air conditioning units are eligible for incentives, as well as the application of window film, which can decrease the cooling load of a facility. Such equipment must meet the minimum qualifying efficiency levels as shown in the table below. These specified energy efficiency qualifications were taken from the Consortium for Energy Efficiency Tier 2 standards for packaged and split system units, and follow ENERGY STAR® criteria for Room air conditioners. PTAC units must be 20% above the Federal Minimum (see the Policies & Procedures for further equipment specifications). The equipment efficiency rating is the rating at full load for the entire system.

Cooling Measures

A

B

C

D

E

Equipment Type

Size Category

Qualifying Efficiency

Equipment Incentive

(per ton)

Efficiency Incentive

(per unit Eff. over Qual Eff., per ton)

Air Cooled AC Units

(Split System and Single Package Units)

< 24,000 Btuh

13.0 SEER

11.6 EER

$25.00

$30.00

 

³ 24,000 Btuh and

< 65,000 Btuh

13.0 SEER

11.6 EER

$25.00

$30.00

 

³ 65,000 Btuh and

< 135,000 Btuh

11.0 EER

11.4 IPLV

$40.00

$30.00

 

³ 135,000 Btuh

£ 240,000 Btuh

10.8 EER

11.2 IPLV

$40.00

$30.00

 

> 240,000 Btuh

10.0 EER

10.4 IPLV

$40.00

$30.00

Water and Evaporative Cooled AC Units

(Split System and Single Package Units)

All Sizes

14.0 EER

$25.00

$80.00

Packaged Terminal AC Units (PTAC) All Sizes

20% above Federal Minimum

$45.00 $15.00

Room Air Conditioners

All Sizes

ENERGY STAR®

$60.00

$25.00

Setback Thermostats

NA

NA

$12.00 per Unit

NA

Window Film

NA

NA

$0.50 per Square Foot

NA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For For AC units, the total incentive is determined by two components – an equipment incentive and an efficiency incentive.  Both the equipment and efficiency incentives are applied per ton of cooling installed.  The equipment qualifies for an equipment incentive if the minimum qualifying efficiency is met for the equipment size category. In addition, the efficiency incentive is added on a prorated basis if the equipment exceeds the minimum qualifying efficiency for the equipment size category. Thus, the Prescriptive cooling incentive is calculated as follows:

Incentive = {Equipment Incentive + Efficiency Incentive (SEER1 new – SEER min)}*tons

1SEER or EER

For example, if an applicant decides to install a 14 SEER 60,000 Btuh (or Btu/hr) rated air-cooled air conditioner, the following steps are taken to calculate the Sure Bet incentive: 

1.      What is the size category for this unit? 

§         The unit is ³ 24,000 Btuh and <65,000 Btuh

§         The Tier 2 standard for this size category is a minimum of 13 SEER or 11.6 EER.

2.      Calculate the tons 

§         Divide equipment Btuh by 12,000 Btuh/ton-hr

§         This unit is 60,000 Btuh/12,000Btu/ton-hr  = 5 tons

3.   Calculate the rebate as follows:

 Incentive = {$25/tonEquip. Incen. + $30/Delta SEER ton Eff. Incen. (14 SEERnew – 13 SEER min)} * 5 tons

    = $275

 

 

Top

Premium Efficiency Motors

Incentives are based on a motor’s nominal full load efficiency published by the Consortium for Energy Efficiency. The incentives are available for motors ranging in size from 1 to 200 horsepower that meet or exceed the efficiency standard listed in the table below.

Prescriptive Motors

 

 

 

 

 

 

Horse

Power

2 POLE/3600 RPM

4 POLE/1800 RPM

6 POLE/1200 RPM

Incentive/ Unit

Open

Closed

Open

Closed

Open

Closed

1

77.0

77.0

85.5

85.5

82.5

82.5

$10.00

2

84.0

84.0

86.5

86.5

86.5

87.5

$15.00

2

85.5

85.5

86.5

86.5

87.5

88.5

$20.00

3

85.5

86.5

89.5

89.5